Go to main content

We are launching a new website! Learn more

Logo

Follow us

Envistar Flex – ThermoCooler HP

Air handling unit with rotary heat exchanger

Air handling unit with integrated controls and a wide range of functional sections. Integrated reversible heat pump with stepless cooling and heating capacity.

Airflow

0.10–13.0 m3/s

18 sizes

High flexibility and large airflow range

IV Produkt Cloud

Can be controlled and monitored via cloud service

Cost-effective

Low installation and operating costs

mollier diagram

Air flow ranges for Envistar Flex

EcoDesign air flow

Technical max air flow

Reversible heat pumpRotorRotor w/ cooling unitCounter-flow exchangerCounter-flow exchanger w/ cooling unitPlate heat exchangerCoil heat exchanger double-stackedCoil heat exchanger
1280
1080
980
850
740
600
480
400
360
300
240
190
150
100
m³/s
0.0
2.0
4.0
6.0
8.0
10.0
12.0

Filter within Envistar Flex

Technical dataforEnvistar Flex with rotary heat exchanger and ThermoCooler HP

Here you will find dimensions and weights as well as power and performance information about Envistar Flex with rotary heat exchanger and ThermoCooler HP .

SizeCooling recoveryAir flow (m3/s)Dimension (mm)Control unit locationEffect and fuse
MinSFPv1,6EcodesignMaxWidthHeightLengthWidth duct connectionHeight duct connectionCooling effect (kW)System voltage
100-2V
-
0.25
0.73
0.93
0.93
1070
1090
2550
700
300
On unit roof
14.9
400VAC
100-4V
Yes
-
-
-
-
-
-
-
-
-
On unit roof
21.9
400VAC
150-2V
-
0.38
1.15
1.23
1.23
1170
1470
2770
800
500
On unit roof
24
400VAC
150-4V
Yes
-
-
-
-
-
-
-
-
-
On unit roof
32.7
400VAC
190-2V
-
0.5
1.61
1.91
2.12
1450
1470
2770
1000
500
On unit roof
30.9
400VAC
190-4V
Yes
-
-
-
-
-
-
-
-
-
On unit roof
44.9
400VAC
240-2V
-
0.58
1.92
2.26
2.48
1450
1686
2990
1000
600
On unit end
32.7
400VAC
240-4V
Yes
-
-
-
-
-
-
-
-
-
On unit end
46.4
400VAC
300-2V
-
0.68
2.44
2.81
2.91
1666
1686
2990
1200
600
On unit end
47
400VAC
300-4V
Yes
-
-
-
-
-
-
-
-
-
On unit end
67.3
400VAC
360-1V
-
0.85
2.63
3.11
3.64
1666
2060
3090
1200
800
On unit end
50.7
400VAC
360-2V
-
0.85
2.63
3.11
3.64
1666
2060
3090
1200
800
On unit end
54.3
400VAC
400-1V
-
0.92
3.26
3.56
3.93
1930
1900
3090
1400
700
On unit end
51.6
400VAC
400-2V
-
0.92
3.26
3.56
3.93
1930
1900
3090
1400
700
On unit end
57.6
400VAC
400-4V
Yes
-
-
-
-
-
-
-
-
-
On unit end
83.4
400VAC
480-1V
-
1.07
3.9
4.38
4.61
2040
2060
3090
1400
800
On unit end
62.9
400VAC
480-2V
-
1.07
3.9
4.38
4.61
2040
2060
3090
1400
800
On unit end
72.9
400VAC
480-4V
Yes
-
-
-
-
-
-
-
-
-
On unit end
104
400VAC
600-2V
-
1.34
4.68
5.34
5.57
2250
2270
3090
1600
800
On unit end
92
400VAC
740-2V
-
1.71
5.95
6.83
7.34
2480
2480
3710
2000
900
In unit next to fan
112.2
400VAC
850-2V
-
1.98
7.25
8.28
8.47
2610
2740
3710
2200
1000
In unit next to fan
128.1
400VAC
980-2V
-
2.38
7.8
8.93
10.05
2860
2980
3710
2400
1100
In unit next to fan
144.6
400VAC
1080-2V
-
2.38
8.45
9.98
10.14
3000
3000
4310
2400
1100
In unit next to fan
162.9
400VAC
1280-2V
-
2.7
9.85
11.16
11.46
3180
3180
4310
2600
1200
In unit next to fan
188.3
400VAC

Technical data for related products

Documentation forEnvistar Flex Rotary Heat Exchanger ThermoCooler HP

Here you will find general documentation for this product series. Download the latest versions of product brochures, instruction manuals, certificates, and other documents.

Your air handling unit

If you are looking for information about your AHU, search using the order number.

Document

Document type

Language

Version

Download/Share

Loading…

Control equipment with proprietary software

The entire range has integrated control equipment with software developed by us. We use Siemens Climatix hardware. The control equipment offers over 100 standard features to choose from so that you can optimise according to your needs. Air flow rates and temperatures can be optimised easily. The units can be connected to the web, IV Produkt Cloud or a parent system (BMS) via multiple communication protocols.

Project-specific electrical and control diagrams are included in the delivery. The unit has been function-tested and is ready for commissioning.

Ongoing projects?

Together, let's find the optimal solution for you!