Go to main content
Logo

Follow us

Envistar Flex

Air handling unit with rotary heat exchanger

Air handling unit with integrated controls and a wide range of functional sections. Integrated cooling unit with stepless cooling capacity.

Why choose Envistar Flex?

Envistar Flex is available with a wide range of functional sections, fans, motors and heat recovery units, providing excellent conditions for energy-optimised air handling.

Envistar Flex can be delivered in sections to facilitate transport into the building. There are also versions that are designed especially to be placed outdoors.

The units are designed for comfort ventilation of premises and are suitable for most types of property, e.g. schools, offices, hotels, shopping centres, industrial premises and hospitals.

Envistar Flex – air handling units with high flexibility. Here in an outdoor version on the roof of battery manufacturer Modine.

Airflow

0.10–13.0 m3/s

18 sizes

High flexibility and large airflow range

IV Produkt Cloud

Can be controlled and monitored via cloud service

Explore IV Produkt Cloud

Cost-effective

Low installation and operating costs

Patented defrosting

ODS Optimised Defrosting System ensures the highest possible annual efficiency

Integrated cooling unit

Option: EcoCooler, also with cooling recovery. Stepless control of cooling power via frequency converter.

Comfort cooling and heat pump in one

Option: The reversible heat pump ThermoCooler HP with stepless control of cooling and heating power

Optimised energy efficiency

Energy optimisation function – ECO

Efficient fans

The fans have PM motors with EC or frequency converter control

Wide selection of sections

Mixing section, recirculation section and much more available as options

For all weather conditions

Available in outdoor configuration

mollier diagram

Air flow ranges for Envistar Flex

EcoDesign air flow

Technical max air flow

Plate heat exchanger w/ cooling unitPlate heat exchangerCounter-flow exchangerCounter-flow exchanger w/ cooling unitRotorRotor w/ cooling unitReversible heat pumpCoil heat exchanger double-stackedCoil heat exchanger
1280
1080
980
850
740
600
480
400
360
300
240
190
150
100
m³/s
0.0
2.0
4.0
6.0
8.0
10.0
12.0

Filter within Envistar Flex

Technical dataforEnvistar Flex with plate heat exchanger and EcoCooler

Here you will find dimensions and weights as well as power and performance information about Envistar Flex with plate heat exchanger and EcoCooler .

SizeAir flow (m3/s)Dimension (mm)Control unit locationWeight (kg)Refrigerant amount (kg)Effect and fuse
MinSFPv1,6EcodesignMaxWidthHeightLengthWidth duct connectionHeight duct connectionR454B Circuit 1R454B Circuit 2R454B Circuit 3tonne CO2e (R454B) Circuit 1tonne CO2e (R454B) Circuit 2tonne CO2e (R454B) Circuit 3Cooling effect (kW)System voltage
100-2V
0.33
0.7
0.45
1
1020
1090
3250
700
300
On unit roof
650
1.8
-
-
0.84
-
-
15
400VAC
150-2V
0.43
1.15
0.9
1.63
1120
1470
3770
800
500
On unit roof
950
2.9
-
-
1.35
-
-
23.7
400VAC
190-2V
0.55
1.5
1.15
2.09
1400
1470
3770
1000
500
On unit roof
1100
3.7
-
-
1.72
-
-
30.6
400VAC
240-2V
0.74
1.8
1.9
2.44
1400
1686
4290
1000
600
On unit end
1300
4.1
-
-
1.91
-
-
32.1
400VAC
300-2V
0.86
2.15
2.2
2.87
1616
1686
4290
1200
600
On unit end
1400
5.1
-
-
2.38
-
-
16.7
400VAC
360-1V
1.19
2.58
2.6
3.71
1616
2060
4690
1200
800
On unit end
1750
6
-
-
2.8
-
-
51.1
400VAC
360-2V
1.19
2.58
2.6
3.71
1616
2060
4690
1200
800
On unit end
1750
6
-
-
2.8
-
-
55.1
400VAC
400-1V
0.95
2.64
2.7
3.65
1880
1900
4390
1400
700
On unit end
1700
7
-
-
3.26
-
-
52.3
400VAC
400-2V
0.95
2.64
2.7
3.65
1880
1900
4390
1400
700
On unit end
1700
7
-
-
3.26
-
-
59.1
400VAC
480-0V
1.53
3.3
3.3
4.66
1990
2060
4690
1400
800
On unit end
2000
8.1
-
-
3.77
-
-
54.9
400VAC
480-1V
1.53
3.3
3.3
4.66
1990
2060
4690
1400
800
On unit end
2000
8.7
-
-
4.05
-
-
62.7
400VAC
480-2V
1.53
3.3
3.3
4.66
1990
2060
4690
1400
800
On unit end
2000
8.7
-
-
4.05
-
-
75.7
400VAC
600-1V
1.7
3.75
3.6
5.78
2200
2270
4690
1600
800
On unit end
2500
8.2
-
-
3.82
-
-
63.1
400VAC
600-2V
1.7
3.75
3.6
5.78
2200
2270
4690
1600
800
On unit end
2500
8.2
-
-
3.82
-
-
76.7
400VAC
600-3V
1.7
3.75
3.6
5.78
2200
2270
4690
1600
800
On unit end
2500
6.2
3.6
-
2.89
1.68
-
90.5
400VAC
740-2V
2.3
5
5.05
7.08
2480
2480
5730
2000
900
In unit next to fan
3250
10.1
-
-
4.71
-
-
81.9
400VAC
740-3V
2.3
5
5.05
7.08
2480
2480
5730
2000
900
In unit next to fan
3250
9.3
4.1
-
4.33
1.91
-
111.6
400VAC
850-1V
2.85
6.5
6.1
8.06
2560
2740
6000
2200
1000
In unit next to fan
3750
11.5
-
-
5.36
-
-
85.5
400VAC
850-2V
2.85
6.5
6.1
8.06
2560
2740
6000
2200
1000
In unit next to fan
3750
9.3
5.8
-
4.33
2.7
-
101.7
400VAC
850-3V
2.85
6.5
6.1
8.06
2560
2740
6000
2200
1000
In unit next to fan
3750
9.3
5.8
-
4.33
2.7
-
127.3
400VAC
980-1V
3.5
8.3
6.9
9.77
2890
3085
6000
2400
1100
In unit next to fan
4250
14.6
-
-
6.8
-
-
89.9
400VAC
980-2V
3.5
8.3
6.9
9.77
2890
3085
6000
2400
1100
In unit next to fan
4250
10.4
7.4
-
4.85
3.45
-
139.7
400VAC
1080-1V
3.66
8
7.1
10.14
3000
3195
6140
2400
1100
In unit next to fan
5300
11.3
7.1
-
5.27
3.31
-
108
400VAC
1080-2V
3.66
8
7.1
10.14
3000
3195
6140
2400
1100
In unit next to fan
5300
11.3
7.1
-
5.27
3.31
-
131.7
400VAC
1080-3V
3.66
8
7.1
10.14
3000
3195
6140
2400
1100
In unit next to fan
5300
7.1
5.8
5.8
3.31
2.7
2.7
158.6
400VAC
1280-1V
4.56
9.4
9.4
11.46
3180
3375
6470
2600
1200
In unit next to fan
6000
12.9
9
-
6.01
4.19
-
119.7
400VAC
1280-2V
4.56
9.4
9.4
11.46
3180
3375
6470
2600
1200
In unit next to fan
6000
12.9
9
-
6.01
4.19
-
145.9
400VAC
1280-3V
4.56
9.4
9.4
11.46
3180
3375
6470
2600
1200
In unit next to fan
6000
9.5
6.7
6.7
4.43
3.12
3.12
185.8
400VAC

Technical data for related products

Documentation forEnvistar Flex Plate Heat Exchanger EcoCooler

Here you will find general documentation for this product series. Download the latest versions of product brochures, instruction manuals, certificates, and other documents.

Your air handling unit

If you are looking for information about your AHU, search using the order number.

Document

Document type

Language

Version

Download/Share

Loading…

Control equipment with proprietary software

The entire range has integrated control equipment with software developed by us. We use Siemens Climatix hardware. The control equipment offers over 100 standard features to choose from so that you can optimise according to your needs. Air flow rates and temperatures can be optimised easily. The units can be connected to the web, IV Produkt Cloud or a parent system (BMS) via multiple communication protocols.

Project-specific electrical and control diagrams are included in the delivery. The unit has been function-tested and is ready for commissioning.

Easy site transportation of Envistar Flex
with ThermoCooler HP

Thanks to the smart solutions of split design for the rotary heat exchanger and the reversible heat pump ThermoCooler HP, this large unit is easily transported through a standard door. To learn more, watch the video and get some helpful tips along the way!

  • Air flow: 4.5 m3/s
  • Unit size (mounted): W 2220 x H 2465 x L 3760 mm
  • Split in: 11 sections
  • Door size: 2100 x 900 mm

Full control with IV Produkt Cloud

IV Produkt Cloud is a cloud service for our air handling units with integrated controls, giving you and your colleagues the ability to monitor your systems wherever you are.

  • Always accessible wherever there is Internet access
  • All systems collected in one place
  • Alarm monitoring via PC or smartphone
  • Possible to analyse and act quickly
  • Control of the indoor climate in your properties everywhere and anytime

Advantages of IV Produkt Cloud

Ongoing projects?

Together, let's find the optimal solution for you!