Go to main content

We are launching a new website! Learn more

Logo

Follow us

Envistar Top – EcoCooler

Air handling unit with rotary heat exchanger and cooling unit

Top-connected air handling unit that saves floor space. Integrated controls and cooling unit with stepless cooling power.

Why choose Envistar Top?

A top-connected duct connection is best suited in approximately 70 per cent of systems with air flow ranges up to 2.8 m3/s.

Envistar Top saves up to 75 per cent of floor space compared to a traditional installation. This makes Envistar Top the most economic and energy-efficient solution for the available floor space. Envistar Top is designed to be able to pass through narrow passages.

Envistar Top – More energy efficient than ever!

Air flow with rotary heat exchanger

0.10–2.80 m3/s

Air flow with counter-flow heat exchanger

0.13–2.80 m3/s

8 sizes

High flexibility and large air flow range

IV Produkt Cloud

Can be controlled and monitored via cloud service

Explore IV Produkt Cloud

Cost-effective

Low installation and operating costs

Patented defrosting

ODS Optimised Defrosting System ensures the highest possible annual efficiency

Integrated cooling unit

Option: EcoCooler with stepless control of cooling power via frequency converter

Comfort cooling and heat pump in one

Option: The reversible heat pump ThermoCooler HP with stepless control of cooling and heating power

mollier diagram

EcoDesign air flow

Technical max air flow

Rotor w/ cooling unitRotorReversible heat pumpCounter-flow exchangerCounter-flow exchanger w/ cooling unit
28
22
17
12
10
09
06
04
m³/s
0.0
0.5
1.0
1.5
2.0
2.5
3.0

Technical dataforEnvistar Top with rotary heat exchanger and EcoCooler

Here you will find dimensions and weights as well as power and performance information about Envistar Top with rotary heat exchanger and EcoCooler .

SizeCooling recoveryAir flow (m3/s)Dimension (mm)Weight (kg)Refrigerant amount (kg)Effect and fuse
MinSFPv1,6EcodesignMaxWidthHeightLengthWidth duct connectionHeight duct connectionR454B Circuit 1tonne CO2e (R454B) Circuit 1R513Atonne CO2e (R513A)Cooling effect (kW)System voltage
04-2V
Yes
0.12
0.35
0.35
0.35
748
1910
1570
500
200
380
-
-
-
-
7.1
400VAC
06-2V
Yes
0.15
0.53
0.61
0.61
890
1910
1720
600
250
440
1.53
0.71
-
-
12.7
400VAC
09-2V
Yes
0.2
0.74
0.9
1
1020
1600
2370
700
300
570
1.89
0.88
-
-
20.8
400VAC
10-2V
Yes
0.2
0.74
0.95
0.97
1020
1980
1990
700
300
550
1.89
0.88
-
-
19.3
400VAC
12-1V
Yes
0.25
1
1.2
1.2
1200
1915
2370
900
300
650
2.15
1
-
-
19.6
400VAC
12-2V
Yes
0.25
1
1.2
1.2
1200
1915
2370
900
300
650
2.15
1
-
-
22.5
400VAC
17-2D
Yes
0.42
1.5
1.8
1.82
1450
1835
3410
1000
350
980
3.69
1.72
-
-
41.7
400VAC
17-2V
Yes
0.41
1.5
1.82
1.82
1450
1835
2670
1000
350
800
-
-
5.1
3.22
32.2
400VAC
22-1V
Yes
0.61
1.75
2.1
2.22
1616
1885
2670
1200
350
980
-
-
5.2
3.28
34
400VAC
22-2D
Yes
0.57
1.9
2.3
2.3
1666
1885
3410
1200
350
1250
5.13
2.39
-
-
61.1
400VAC
22-2V
Yes
0.61
1.75
2.1
2.22
1616
1885
2670
1200
350
980
-
-
5.2
3.28
37.9
400VAC
28-1V
-
0.8
2.67
2.8
3
1930
2095
3090
1400
350
1300
7.02
3.27
-
-
48.6
400VAC
28-1V
Yes
0.8
2.67
2.8
3
1930
2095
3510
1400
350
1400
7.02
3.27
-
-
68.6
400VAC
28-2V
-
0.92
2.67
2.8
3
1930
2095
3090
1400
350
1300
7.02
3.27
-
-
54.5
400VAC
28-2V
Yes
0.92
2.67
2.8
3
1930
2095
3510
1400
350
1400
7.02
3.27
-
-
75.9
400VAC

Technical data for related products

Documentation forEnvistar Top Rotary Heat Exchanger EcoCooler

Here you will find general documentation for this product series. Download the latest versions of product brochures, instruction manuals, certificates, and other documents.

Your air handling unit

If you are looking for information about your AHU, search using the order number.

Document

Document type

Language

Version

Download/Share

Brochure

English

1

Brochure

English

3

Connection instructions

English

05

Assembly instruction

English

04

Assembly instruction

English

00

Assembly instruction

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Configuration and settings

English

-

-

Certificates and declarations

English

-

-

-

English

-

-

Certificates and declarations

English

-

2025

Control equipment with proprietary software

The entire range has integrated control equipment with software developed by us. We use Siemens Climatix hardware. The control equipment offers over 100 standard features to choose from so that you can optimise according to your needs. Air flow rates and temperatures can be optimised easily. The units can be connected to the web, IV Produkt Cloud or a parent system (BMS) via multiple communication protocols.

Project-specific electrical and control diagrams are included in the delivery. The unit has been function-tested and is ready for commissioning.

Ongoing projects?

Together, let's find the optimal solution for you!